UPC WSFU & Drainage Table

UPC Table 703.2 fixture unit values for both water supply (WSFU) and drainage (DFU) sizing.

Introduction

The UPC Table 703.2 provides maximum unit loading and maximum length for drainage and vent piping. It also defines WSFU values for water supply sizing. These values differ from IPC values.

UPC Table 703.2 - Maximum Unit Loading and Maximum Length

Pipe Size (in)Max DFU VerticalMax DFU HorizontalMax Length Vertical (ft)Max DFU VentMax Length Vent (ft)
1-1/41145145
1-1/22165860
21688524120
3483521284212
4256216300256300
5600428390600390
613807205101380510
8360026407503600750
1056004680---
1284008200---

UPC Appendix C Table C304.3 - Horizontal Fixture Branches and Stacks

Pipe Size (in)Horizontal BranchOne Stack (<=3 Branch Intervals)Stack (>3 Intervals) TotalStack (>3) One Interval
1-1/23482
2610246
2-1/21220429
320487220
416024050090
53605401100200
66209601900350
8140022003600600
102500380056001000
123900600084001500

Notes

  • For 1/8" per foot slope, multiply horizontal DFU values by 0.8.
  • UPC values differ from IPC values for the same pipe sizes.
  • Vent pipe sizing uses the same table with separate columns.