UPC Drainage Sizing Tables
UPC Appendix C Table C304.2 building drain sizing: DFU capacity by pipe size and slope.
Introduction
The UPC Appendix C provides drainage sizing tables. Table C304.2 sizes building drains and sewers based on DFU and slope. Table C304.3 sizes horizontal fixture branches and stacks.
UPC Appendix C Table C304.2 - Building Drains and Sewers
| Pipe Dia (in) | 1/16" slope | 1/8" slope | 1/4" slope | 1/2" slope |
|---|---|---|---|---|
| 2 | - | - | 21 | 26 |
| 2-1/2 | - | - | 24 | 31 |
| 3 | - | 20 | 42 | 50 |
| 4 | - | 180 | 216 | 250 |
| 5 | - | 390 | 480 | 575 |
| 6 | - | 700 | 840 | 1000 |
| 8 | 1400 | 1600 | 1920 | 2300 |
| 10 | 2500 | 2900 | 3500 | 4200 |
| 12 | 3900 | 4600 | 5600 | 6700 |
| 15 | 7000 | 8300 | 10000 | 12000 |
Notes
- • Values are maximum DFU allowed for each pipe size at the given slope.
- • 1/16" per foot slope is only permitted for pipes 8" and larger.
- • Slope requirements: 1/4" per foot for pipes <3", 1/8" per foot for pipes >=3".
Related Articles
UPC Pipe Sizing Guide
How the Uniform Plumbing Code sizes water supply pipes using WSFU tables, and how Plumbing Booster applies UPC-specific values for both water supply and drainage.
Drainage Pipe Sizing Reference
Complete reference for drainage pipe sizing using IPC Table 710.1 and UPC Table 703.2, including slope requirements and maximum length limitations.
Sanitary Drainage Design Guide
Sanitary drainage system design involves sizing waste pipes using Drainage Fixture Units (DFU), selecting appropriate slopes, and ensuring venting adequacy.
Want to try these calculations yourself?
Download Plumbing Booster Free Trial →Ready to design smarter?
Start your 28-day free trial today. No credit card required.