Water Supply

IPC Pipe Sizing Tables

IPC Table E104.1 minimum pipe sizes and Table E103.3(3) WSFU-to-GPM conversion for water supply sizing.

Introduction

The IPC provides two key tables for pipe sizing: Table E103.3(3) converts WSFU to GPM flow rates, and Table E104.1 specifies minimum pipe sizes for water meters, mains, and distribution piping.

IPC Table E103.3(3) - Supply System Demand (Flush Tank)

WSFUGPMWSFUGPMWSFUGPM
13201920060
25302330075
37402740085
59503050095
101470351000125
1517100432000180

IPC Table E104.1 - Minimum Pipe Sizes (Selected)

WSFUMin Pipe SizeMax Length (ft)Flow (GPM)
13/8"503
23/8"505
31/2"607
51/2"709
101/2"8014
203/4"10019
301"13023
501"20030
701-1/4"25035
1001-1/4"30043
2002"40060

Notes

  • Table E103.3(3) has separate columns for flush tank and flushometer systems.
  • The conversion is non-linear due to diversity factor.
  • Table E104.1 values are minimums - velocity checks may require larger pipes.