IPC Pipe Sizing Tables
IPC Table E104.1 minimum pipe sizes and Table E103.3(3) WSFU-to-GPM conversion for water supply sizing.
Introduction
The IPC provides two key tables for pipe sizing: Table E103.3(3) converts WSFU to GPM flow rates, and Table E104.1 specifies minimum pipe sizes for water meters, mains, and distribution piping.
IPC Table E103.3(3) - Supply System Demand (Flush Tank)
| WSFU | GPM | WSFU | GPM | WSFU | GPM |
|---|---|---|---|---|---|
| 1 | 3 | 20 | 19 | 200 | 60 |
| 2 | 5 | 30 | 23 | 300 | 75 |
| 3 | 7 | 40 | 27 | 400 | 85 |
| 5 | 9 | 50 | 30 | 500 | 95 |
| 10 | 14 | 70 | 35 | 1000 | 125 |
| 15 | 17 | 100 | 43 | 2000 | 180 |
IPC Table E104.1 - Minimum Pipe Sizes (Selected)
| WSFU | Min Pipe Size | Max Length (ft) | Flow (GPM) |
|---|---|---|---|
| 1 | 3/8" | 50 | 3 |
| 2 | 3/8" | 50 | 5 |
| 3 | 1/2" | 60 | 7 |
| 5 | 1/2" | 70 | 9 |
| 10 | 1/2" | 80 | 14 |
| 20 | 3/4" | 100 | 19 |
| 30 | 1" | 130 | 23 |
| 50 | 1" | 200 | 30 |
| 70 | 1-1/4" | 250 | 35 |
| 100 | 1-1/4" | 300 | 43 |
| 200 | 2" | 400 | 60 |
Notes
- • Table E103.3(3) has separate columns for flush tank and flushometer systems.
- • The conversion is non-linear due to diversity factor.
- • Table E104.1 values are minimums - velocity checks may require larger pipes.
Related Articles
IPC Pipe Sizing Guide
Step-by-step explanation of the IPC table-based pipe sizing method, from WSFU summation through flow conversion to final pipe selection using Table E104.1.
WSFU Calculation Guide
Understanding WSFU is fundamental to plumbing design. This guide explains what WSFU are, how different codes define them, and how Plumbing Booster uses them for pipe sizing.
Want to try these calculations yourself?
Download Plumbing Booster Free Trial →Ready to design smarter?
Start your 28-day free trial today. No credit card required.